Back to Calculators
Engineering Tool

Short Circuit Calculator

Calculate prospective short circuit current and verify cable thermal withstand capacity. Ensure cables survive fault conditions without insulation damage or conductor failure.

📐 Standard: IEC 60909 / IEC 60364-4-43 🔥 Thermal: Adiabatic heating model Check: I²t ≤ k²S²
📥

Input Parameters

Transformer + upstream impedance. Typical LV: 20–80 mΩ
Must be a positive number
Must be a positive number
Typical: 0.1s (HV), 0.4s (LV MCB), 1.0s (LV fuse)
📊

Calculation Results

Enter parameters above and click Calculate

📋

Thermal Withstand by Cable Size

Maximum fault current each cable size can withstand for the specified fault duration.

Size (mm²) Max Isc (kA) k²S² (A²s) Withstand
ℹ️

Assumptions & Notes

Input Summary

Voltage
Source Impedance
Cable Size
Conductor
Length
Fault Time

Engineering Notes

⚠️ Thermal withstand condition: I²sc × t ≤ k² × S². Where k is the material constant (143 Cu/XLPE, 115 Cu/PVC, 94 Al/XLPE, 76 Al/PVC).
📌 Short circuit current calculation uses IEC 60909 simplified method: Isc = c × Un / (√3 × Ztotal), where c = 1.05 (LV) or 1.1 (MV).